Free Heat Pump Tool

Heat Pump Breaker & Wire Size Calculator

Find the breaker amperage and copper wire gauge from your heat pump nameplate (MCA & MOCP).

✓ 100% free · no signup✓ Based on US DOE / ENERGY STAR✓ Instant results

Size from the nameplate, not the tonnage

The correct breaker and wire size come from two numbers on the heat pump's rating plate (nameplate), not from its tonnage: MCA (Minimum Circuit Ampacity) sizes the wire, and MOCP (Maximum Overcurrent Protection) sets the largest allowable breaker. Enter those above for the answer.

Copper wire size by MCA (75°C)

MCACopper wireTypical breaker (MOCP)
≤ 20 A#12 AWG20 A max
≤ 30 A#10 AWG30 A max
≤ 40 A#8 AWG40–45 A
≤ 55 A#6 AWG50–60 A
⚠️ Never use a breaker larger than the MOCP, and always size wire to the MCA per the NEC 75°C column. Heat pump circuits are usually 240 V, two-pole.

Rough guide by size (estimate only)

If you do not have the nameplate, residential heat pumps commonly land around: 1.5–2 tons → 20–30 A breaker / #10 wire; 2.5–3 tons → 30–40 A / #10–#8; 3.5–5 tons → 40–60 A / #8–#6. These are estimates only — the nameplate MCA/MOCP and a licensed electrician are the authority, and all work must meet the NEC and local code.

Frequently asked questions

What size breaker for a heat pump?

Use a breaker no larger than the nameplate MOCP (Max Overcurrent Protection) — commonly 30–50 A for residential heat pumps. Never exceed the MOCP.

What size wire for a heat pump?

Size the copper wire to the nameplate MCA (Minimum Circuit Ampacity) using the NEC 75°C column — e.g. 25 A MCA → #10 AWG, 40 A → #8. Always verify with the nameplate.

Where do I find MCA and MOCP?

On the heat pump rating plate (nameplate) on the outdoor unit. These two numbers, not the tonnage, determine the breaker and wire.

Can I use a 30-amp breaker for a heat pump?

Only if the nameplate MOCP is 30 A or higher and the MCA fits #10 wire. Never exceed the MOCP printed on the unit.

Does a heat pump need a dedicated circuit?

Yes — the outdoor unit needs its own dedicated 240-volt circuit sized to its nameplate; the indoor air handler usually has a separate circuit.

Related calculators

⚠️ Rule-of-thumb estimate, not a substitute for a professional Manual J load calculation. Based on US DOE / ENERGY STAR guidance.